楼主以前用WINCC 7.1版本单独安装后打开项目没有问题,现在为了装PCS7把旧版本协助了,用PCS 7 8.1版本安装软件,安装的WINCC7.3创建新项目失败,因为项目管理器无法启动基本应用程序XREF。进PCS7 把WINCC组件卸载了重装还是那样。该怎么办呢???
问题补充:
SQL Server(WinCC)已经设置为自动并且启动了
图片说明:
最佳答案
看看SQL Server(WinCC)是否启动了?
有使用远程桌面等远程软件吗?
参考下:
I have encountered this problem. If your problem happens locally and not on remote connection I think this can solve your problem.
I assume you have done something on the Microsoft SQL Server Surface Area Configuration tool called "SQL Server Surface Area Configuration". Go to this tool on the Start menu > Microsoft SQL Server 20XX > Configuration Tools > SQL Server Surface Area Configuration.
Then on the Services and Connections link. Check the "WinCC > Database Engine > Remote Connections" if it is using remote connections with TCP/IP and Named pipes. I just disabled the Remote connections and just changed to "Local connections only" since I still don''t need remote connections. Don''t forget to restart after making this change. I tried this without restarting and still received the error. But after restart it is completely gone.
This solved my problem. Please rate if this becomes helpful. I still haven''t got any rating haha.
提问者对于答案的评价:
谢谢,重装后解决的