cpu报警消息

plc停止运行,cpu消息如下:
 Event 3 of 10:  Event ID 16# 4301
 Mode transition from STOP to STARTUP 
 STOP due to: Power failure
 Startup information: 
 - Time for time stamp at the last backed up power on
 - Single processor operation
 Current/last startup type:
 - Automatic warm restart after backed up power on
 Permissibility of certain startup types: 
 - Manual warm restart permitted
 - Automatic warm restart permitted
 Last valid operation or setting of the automatic startup type at power on:
 - Automatic warm restart after backed up power on
 Previous operating mode: STOP (internal)
 Requested operating mode: STARTUP (warm restart)
 Incoming event
 05:21:08.492 PM  10/20/1995

 
 Event 4 of 10:  Event ID 16# 38C4
 Distributed I/Os: station return
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:  32767
 Requested OB: Rack failure OB (OB86)
 OB not found, or disabled, or cannot be started in the current operating mode
 External error, Outgoing event
 05:20:59.004 PM  10/20/1995

 
 Event 5 of 10:  Event ID 16# 5371
 Distributed I/Os: end of the synchronization with a DP master 
 Slot of the DP master:   2 
 Number of distributed stations:   1
 Incoming event
 05:20:57.522 PM  10/20/1995

 
 Event 6 of 10:  Event ID 16# 4300
 Power on backed up 
 Previous operating mode: No voltage
 Requested operating mode: STOP (own initialization)
 Incoming event
 05:20:54.038 PM  10/20/1995

 
 Event 7 of 10:  Event ID 16# 494E
 Power failure
 Previous operating mode: STOP (internal)
 Requested operating mode: No voltage
 External error, Incoming event
 05:20:41.034 PM  10/20/1995

 
 Event 8 of 10:  Event ID 16# 38C4
 Distributed I/Os: station return
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:   2047
 Requested OB: Rack failure OB (OB86)
 OB not found, or disabled, or cannot be started in the current operating mode
 External error, Outgoing event
 05:20:02.164 PM  10/20/1995

 
 Event 9 of 10:  Event ID 16# 456F
 STOP caused by rack failure (OB not loaded or not possible, or no FRB) 
 Breakpoint in user program: Cyclic program (OB1) 
 Priority class:    1
 FC number:      2
 Module address:    246
 Previous operating mode: RUN
 Requested operating mode: STOP (internal)
 Internal error, Incoming event
 05:20:00.718 PM  10/20/1995

 
 Event 10 of 10:  Event ID 16# 39C4
 Distributed I/Os: station failure
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:   2047
 Requested OB: Rack failure OB (OB86)
 Priority class: 26
 External error, Incoming event
 05:20:00.705 PM  10/20/1995
 不知问题出在那,那位高手解释一下万分感谢!

 
 

最佳答案

1。首先PLC的诊断提示是:25#DP slave机架站号(即DP地址号)有故障,但又缺少OB86块(机架故障组织块),从而导致CPU中断停机;
 2。诊断提示中还列出由OB1块调用执行的FC2用户程序功能块可能有程序执行错误,导致CPU中断停机;
   因此,我建议你按的如下两项方法处理:
 1。首先将OB8X系列诊断组织块(例如OB80、OB81、OB82、OB83、OB84、OB85、OB86、OB88和OB121、OB122)下载至PLC中,可有效避免CPU的异常停机;
 2。然后仔细检查由OB1块调用执行的FC2用户程序功能块,是否有编程逻辑错误(例如:访问了实际不存在的存储地址编号、指针或数组索引号不存在,或超限等原因)。

提问者对于答案的评价:
可能是机架问题。

原创文章,作者:ximenziask,如若转载,请注明出处:https://www.zhaoplc.com/plc351854.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2021年7月5日
下一篇 2021年7月5日

相关推荐

发表回复

登录后才能评论