描述
在SIMATIC BATCH 6.1服务器(主服务器和备用服务器)上,如果以高级用户(power user)登录,在Windows事件查看器中会出现错误记录。
当启动BATCH主服务器的时候,在事件查看器中会产生如下记录 (source: DCOM, Event ID: 10006) :
DCOM has received an error "General "Access denied" error" from the computer "<computer name>" as an attempt was made to activate the following server: |
当启动BATCH备用服务器的时候,在事件查看器中会产生如下记录 (source: DCOM, Event ID: 10015) :
The computer-wide limit settings deny the SID {<SID>} for user <computer name>/<user name> start authorization (remote) for the COM server application with CLSID {<CLSID>}. This security authorization can be changed with the administration program for component services. |
指导
要避免DCOM错误,需要把所有的高级用户添加到 "Distributed COM user" 用户组。在SIMATIC Logon网络的所有计算机上都要做这样的配置。
创建环境
这篇FAQ在Windows Server 2003 SP2 和 SIMATIC BATCH V6.1 SP3环境下创建。
关键词