What to consider regarding communication of SIWAREX CS inside a ET200S Profibus-DP station?

n

QUESTION:
What to consider regarding communication of SIWAREX CS inside a ET200S Profibus-DP station?n

ANSWER:
In case of a non-working data-record communication between the Standard- / HighFeature- / CPU-station and the SIMATIC CPU, the DP Interrupt Mode ( 50 KB ) of the ET200S has to be checked inside the hardware configuration.n

ATTENTION: Not every ET200S station supports the whole communication between SIWAREX CS and SIMATIC CPU!n

In general the following ET200S-stations can be used with SIWAREX CS:

PROFIBUS

IM 151-1 Basic

from 6ES7 151-1CA00-0AB0 onwards

ET200S Compact 16DI/16DO

from 6ES7 151-1CA00-3BL0 onwards

ET200S Compact 32DI

from 6ES7 151-1CA00-1BL0 onwards

IM151-1 Standard

from 6ES7 151-1AA02-0AB0 onwards

IM151-1 FO Standard

from 6ES7 151-1AB02-0AB0 onwards

IM151-1 High Feature

from 6ES7 151-1BA00-0AB0 onwards

PROFIBUS-CPU

IM151-7 CPU FO

from 6ES7 151-7AB00-0AB0 onwards

IM151-7 CPU

from 6ES7 151-7AA10-0AB0 Version 2.1 onwards

PROFIBUS-F-CPU

IM151-7 F-CPU

from 6ES7 151-7FA00-0AB0 onwards

PROFINET

IM151-3 PN Standard

from 6ES7 151-3AA20-0AB0 onwards

IM151-3 PN High Feature

from 6ES7 151-3BA20-0AB0 onwards

IM151-3 PN FO

from 6ES7 151-3BB21-0AB0 onwards

PROFINET-CPU

IM151-8 PN/DP CPU

from 6ES7 151-8AB00-0AB0 onwards

PROFINET-F-CPU

IM151-8F PN/DP

from 6ES7 151-8FB00-0AB0 onwards

Following ET200S-stations support the data-record communication additionally:

PROFIBUS

IM151-1 Standard

from 6ES7 151-1AA04-0AB0 onwards *

IM151-1 FO Standard

from 6ES7 151-1AB05-0AB0 onwards *

IM151-1 High Feature

from 6ES7 151-1BA00-0AB0 onwards

PROFIBUS-CPU

IM151-7 CPU FO

from 6ES7 151-7AB00-0AB0 onwards

IM151-7 CPU

from 6ES7 151-7AA10-0AB0 version 2.1 onwards

PROFIBUS-F-CPU

IM151-7 F-CPU

from 6ES7 151-7FA00-0AB0 onwards

PROFINET

IM151-3 PN Standard

from 6ES7 151-3AA20-0AB0 onwards

IM151-3 PN High Feature

from 6ES7 151-3BA20-0AB0 onwards

IM151-3 PN FO

from 6ES7 151-3BB21-0AB0 onwards

PROFINET-CPU

IM151-8 PN/DP CPU

from 6ES7 151-8AB00-0AB0 onwards

PROFINET-F-CPU

IM151-8F PN/DP

from 6ES7 151-8FB00-0AB0 onwards

* = with older versions data-record communication is not possible.

IM151-1 Basic, ET200S Compact 16DI/16DO and ET200S Compact 32DI doesn’t support the data-record communication at all. With these you can only use the FB without data-record communication.