QUESTION:
What to consider regarding communication of SIWAREX CS inside a ET200S Profibus-DP station?n
ANSWER:
In case of a non-working data-record communication between the Standard- / HighFeature- / CPU-station and the SIMATIC CPU, the DP Interrupt Mode ( 50 KB ) of the ET200S has to be checked inside the hardware configuration.n
ATTENTION: Not every ET200S station supports the whole communication between SIWAREX CS and SIMATIC CPU!n
In general the following ET200S-stations can be used with SIWAREX CS:
PROFIBUS | IM 151-1 Basic | from 6ES7 151-1CA00-0AB0 onwards |
ET200S Compact 16DI/16DO | from 6ES7 151-1CA00-3BL0 onwards | |
ET200S Compact 32DI | from 6ES7 151-1CA00-1BL0 onwards | |
IM151-1 Standard | from 6ES7 151-1AA02-0AB0 onwards | |
IM151-1 FO Standard | from 6ES7 151-1AB02-0AB0 onwards | |
IM151-1 High Feature | from 6ES7 151-1BA00-0AB0 onwards | |
PROFIBUS-CPU | IM151-7 CPU FO | from 6ES7 151-7AB00-0AB0 onwards |
IM151-7 CPU | from 6ES7 151-7AA10-0AB0 Version 2.1 onwards | |
PROFIBUS-F-CPU | IM151-7 F-CPU | from 6ES7 151-7FA00-0AB0 onwards |
PROFINET | IM151-3 PN Standard | from 6ES7 151-3AA20-0AB0 onwards |
IM151-3 PN High Feature | from 6ES7 151-3BA20-0AB0 onwards | |
IM151-3 PN FO | from 6ES7 151-3BB21-0AB0 onwards | |
PROFINET-CPU | IM151-8 PN/DP CPU | from 6ES7 151-8AB00-0AB0 onwards |
PROFINET-F-CPU | IM151-8F PN/DP | from 6ES7 151-8FB00-0AB0 onwards |
Following ET200S-stations support the data-record communication additionally:
PROFIBUS | IM151-1 Standard | from 6ES7 151-1AA04-0AB0 onwards * |
IM151-1 FO Standard | from 6ES7 151-1AB05-0AB0 onwards * | |
IM151-1 High Feature | from 6ES7 151-1BA00-0AB0 onwards | |
PROFIBUS-CPU | IM151-7 CPU FO | from 6ES7 151-7AB00-0AB0 onwards |
IM151-7 CPU | from 6ES7 151-7AA10-0AB0 version 2.1 onwards | |
PROFIBUS-F-CPU | IM151-7 F-CPU | from 6ES7 151-7FA00-0AB0 onwards |
PROFINET | IM151-3 PN Standard | from 6ES7 151-3AA20-0AB0 onwards |
IM151-3 PN High Feature | from 6ES7 151-3BA20-0AB0 onwards | |
IM151-3 PN FO | from 6ES7 151-3BB21-0AB0 onwards | |
PROFINET-CPU | IM151-8 PN/DP CPU | from 6ES7 151-8AB00-0AB0 onwards |
PROFINET-F-CPU | IM151-8F PN/DP | from 6ES7 151-8FB00-0AB0 onwards |
* = with older versions data-record communication is not possible.
IM151-1 Basic, ET200S Compact 16DI/16DO and ET200S Compact 32DI doesn’t support the data-record communication at all. With these you can only use the FB without data-record communication.