3UA6热继电器不同的测试功能rnDifferent test functions of 3UA6 overcurrent relays

问题:

为什么同样的3UA6存在两种不同的测试功能的方式?Why is it possible that 3UA6 overcurrentrelays of same type have different test functions?

解答:

最早生产的产品测试功能如下:(1990/91之前生产的产品)

按下TEST按钮,NC触点(95/96)打开,当松开该按钮后,95/96触点再次闭合。这个特性可以作为一个工具来测试控制回路发生短路后的触点状态。

1990/91年以后生产的3UA6热继电器的测试功能如下:

按下TEST按钮,热继电器将保持在TRIP位置,直到按下RESET按钮后,热继电器触点才会恢复到正常状态。

Originally(up to manufacturing time 1990/91) the test function was as follows:
By pressing TEST button the N/C contact 95/96 was opened. After releasing thisbutton, contact 95/96 closed again.
Thisfeature served as a facility for testing the contact after occurance of ashort-circuit in the control circuit.

3UA6 overcurrent relays manufactured after 1990/91 incorporate the followingTEST function:
By pressing TEST button the overcurrent relay latches into TRIP-position.
By operation ofRESET-button the overcurrent relay regains normal status.