问题:
3RW30/40/44 软起动器输入控制端电缆的长度(距离)是多少?
回答:
最长允许的距离请参照下表
Cable lengths for the control circuit inputs - 3RW soft starters |
|||
|
|
||
Soft starter |
Size |
Control supply voltage |
Distance (m) |
3RW44 |
1-5 |
115 V AC |
500 |
3RW44 |
1-5 |
230 V AC |
500 |
3RW40 |
S6-S12 |
115 V AC |
500 |
3RW40 |
S6-S12 |
230 V AC |
500 |
3RW40 |
S0-S3 |
24 V AC |
20 |
3RW40 |
S0-S3 |
24 V DC |
500 |
3RW40 |
S0-S3 |
230 V AC |
20 |
3RW40 |
S0-S3 |
230 V DC |
500 |
3RW30 |
S0-S3 |
24 V AC |
20 |
3RW30 |
S0-S3 |
24 V DC |
500 |
3RW30 |
S0-S3 |
230 V AC |
20 |
3RW30 |
S0-S3 |
230 V DC |
500 |