Diagnostic buffer of module CPU 315-2 DP
Order No./ Description Component Version
6ES7 315-2AH14-0AB0 Hardware 2
- - - Firmware V 3.0.3
Boot Loader Firmware expansion A 25.7.5
Rack: 0
Slot: 2
Serial number: S C-B2UB70082011
Event 1 of 500: Event ID 16# 4541
STOP caused by priority class system
Event: Cycle time exceeded
OB number: Timing error OB (OB80)
Priority class: 26
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
02:09:37.079 AM 04/18/1994
Event 2 of 500: Event ID 16# 3501
Cycle time exceeded
Run time of the last cycle (ms): 6000
Cause: OB1 start event initiated by end of warm restart
Causing OB: Cyclic program (OB1)
Causing priority class: 1
Requested OB: Timing error OB (OB80)
Priority class: 26
Internal error, Incoming event
02:09:31.079 AM 04/18/1994
最佳答案
Cycle time exceeded
Run time of the last cycle (ms): 6000
Cause: OB1 start event initiated by end of warm restart
Causing OB: Cyclic program (OB1)
上述信息表明有循环时间超时的错误,检查OB1中程序是否有死循环的现象。
Timing error OB (OB80):
在诊断信息描述中调用了OB80。
OB80 :时间故障。可能的原因:
这样的故障包括: 循环时间超出、执行OB 时应答故障、向前移动时间以致于跃过了OB 的启动时间、CiR 后恢复RUN 方式。如果,例如,当循环中断OB 仍在执行前一次调用时,该OB 块的启动事件发生,操作系统调用OB80。如果OB80 未编程,CPU 变为STOP 方式。您可以使用SFC39 至42 封锁或延时和再使能时间故障OB。