MD720-3的GPRS通讯问题

MD720-3上面的S,Q等都会一直亮,但C灯从来都没亮过,看说明书上说是因为没有和服务器连接,下面是我按照说明书写的程序,请各位大侠看看有什么不对的地方没
Network 1 // 网络标题
// 网络注释
LD     SM0.0
CALL   SBR1, 1, &VB700, &VB720, &VB730, &VB740, &VB750, &VB760, &VB770, &VB780, &VB790, &VB809, V810.0, V810.1, V810.2, VW812
Network 2 
LD     SM0.0
=      L60.0
LD     M10.0
=      L63.7
LD     L60.0
CALL   SBR2, L63.7, VW814, VW816, VB818, 1, 0, V810.3, V810.4, V810.5, VW822
Network 3 
LD     SM0.0
CALL   SBR3, 0, VW824, VW826, VW828, VW830, VB832, V810.6
Network 4 
LD     SM0.0
=      L60.0
LDN    SM0.0
=      L63.7
LDN    SM0.0
=      L63.6
LD     L60.0
CALL   SBR4, L63.7, L63.6, 0, 10, VW834, V810.7, V811.0, V811.1, VW836
Network 5 
LDN    M10.0
TON    T40, +50
Network 6 
LD     SM0.0
A      T40
=      M10.0
Network 7 
LD     SM0.0
MOVW   +0, VW814
Network 8 
LD     SM0.0
MOVW   +3000, VW816
Network 9 
LD     SM0.0
MOVW   +10, VW818
Network 10 
LD     SM0.0
MOVW   +3000, VW816
Network 11 
LD     SM0.0
MOVW   +2000, VW824
Network 12 
LD     SM0.0
MOVW   +10, VW826
MD720-3里面插入的是联通的手机卡,
主机是用的笔记本,用联通的3G无线上网卡上的网
下面是我建的数据块
VB700  "?"
VB720  "26862"
VB730  "modem1"
VB740  "secret1"
VB750  "1234"
VB760  "cmnet"
VB770  "?"
VB780  "?"
VB790  "?"
VB809  "?"
里面打?的都应该怎样填?
VB720的端口号应该怎样处理,用3G无线上网卡上网时这个端口号都应该在哪里设置

最佳答案

S\Q灯亮,说明MD720-3模块已经成功登陆到GPRS网络;C灯从未亮过说明从未与SINAUT SC软件建立过连接,出现这样的问题,一般先考虑你的中央站的IP地址,也就是VB700的设置;联通的3G卡未用过,不知道3G无线卡上网的时候,你的IP地址给你分配的是内网地址还是公网地址呀,若是公网地址,VB700就设置这个公网地址就行了,若是内网地址你就需要考虑端口映射了。其实可以采用ADSL拨号试试,ADSL拨号的时候一般都是分配的动态公网地址,这时修改VB700,下载程序测试。
参考西门子下载中心文档编号:A0100.

提问者对于答案的评价:
谢谢指点,现在已经连上了

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc301217.html