300PLC 一直报FC105

下载程序后出现  
Diagnostic buffer of module CPU 314C-2 DP

Order No./ Description         Component                      Version                       
6ES7 314-6CH04-0AB0            Hardware                       6                             
- - -                          Firmware                       V 3.3.12                      
Boot Loader                    Firmware expansion             A 37.12.12                    

Rack:                          0
Slot:                          2


Serial number: S C-K7ND04442018


Event 1 of 127:  Event ID 16# 4562
STOP caused by programming error (OB not loaded or not possible, or no FRB) 
FC number:    105
Module address:    192
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
01:06:52.263 AM  01/01/1994
(Coding: 16# 4562  FF84  8C00  0101  0069  00C0)


Event 2 of 127:  Event ID 16# 2523
Area length error when writing
M area, word access, Access address:    300
Requested OB: Programming error OB (OB121)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
01:06:52.260 AM  01/01/1994
(Coding: 16# 2523  FE79  0023  012C  0000  0000)


Event 3 of 127:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered via MPI; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered via MPI; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
01:06:52.255 AM  01/01/1994
(Coding: 16# 4302  FF68  C700  0000  0814  7714)


Event 4 of 127:  Event ID 16# 1381
Request for manual warm restart 
STOP due to: STOP caused by programming error (OB not loaded or not possible, or no FRB)
Startup information:
- Startup without modified system configuration 
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered via MPI; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered via MPI; last power on backed up 
Requested OB: Startup OB (OB100)
OB not found, or disabled, or cannot be started in the in the current operating mode
Incoming event
01:06:52.255 AM  01/01/1994
(Coding: 16# 1381  FE64  C772  4562  0814  7714)

最佳答案

1、参考:
http://www.ad.siemens.com.cn/service/answer/NewHl/HlQuestionInfo.aspx?Q_ID=189680&cid=1029
2、可以通过下载OB82,OB85,OB86,OB121,OB122来避免故障停机。
《300 CPU诊断》
http://www.ad.siemens.com.cn/productportal/prods/published/300list/Diag_list2.html
《300 诊断》
http://www.ad.siemens.com.cn/productportal/prods/published/300list/diag_list0.html

提问者对于答案的评价:
加了OB121好了

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc288110.html