CPU 315-2 DP系统故障

故障诊断如下:
Diagnostic buffer of module CPU 315-2 DP
Event 1 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:   2000
Requested OB: I/O access error OB (OB122)
Priority class:  1
External error, Incoming event
04:28:25.010 AM  11/21/2012
(Coding: 16# 2942  017A  0020  07D0  0000  0000)
Event 2 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:   2000
Requested OB: I/O access error OB (OB122)
Priority class:  1
External error, Incoming event
04:28:25.010 AM  11/21/2012
(Coding: 16# 2942  017A  0020  07D0  0000  0000)
Event 3 of 10:  Event ID 16# 2942
I/O access error, reading
P area, word access, Access address:   2000
Requested OB: I/O access error OB (OB122)
Priority class:  1
External error, Incoming event
04:28:25.010 AM  11/21/2012
(Coding: 16# 2942  017A  0020  07D0  0000  0000)
Event 4 of 10:  Event ID 16# 2942
I/O access error, reading P area, word access, Access address:   2000
Requested OB: I/O access error OB (OB122)
Priority class:  1
External error, Incoming event
04:28:25.009 AM  11/21/2012
(Coding: 16# 2942  017A  0020  07D0  0000  0000)
Event 5 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    138
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  008A  0000  0000)
Event 6 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    136
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  0088  0000  0000)
Event 7 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    134
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  0086  0000  0000)
Event 8 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    132
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  0084  0000  0000)
Event 9 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    130
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  0082  0000  0000)
Event 10 of 10:  Event ID 16# 2523
Area length error when writing
Instance DB, word access, Access address:    128
Requested OB: Programming error OB (OB121)
Priority class:  1
Internal error, Incoming event
04:28:25.006 AM  11/21/2012
(Coding: 16# 2523  0179  0025  0080  0000  0000)
请帮忙分析一下

问题补充:
Diagnostic buffer of module CPU 315-2 DP

Order No./ Description         Component                      Version                       
6ES7 315-2AH14-0AB0            Hardware                       2                             
- - -                          Firmware                       V 3.0.3                       
Boot Loader                    Firmware expansion             A 25.7.5                      

Rack:                          0
Slot:              &nb

专家建议

"老柳树" 你好!

  从诊断缓冲区内容来看,问题主要有以下几点:

1.I/O访问错误,程序*问到了PIW2000的地址,但是实际模块并不存在,例如:模块没有插入或者模块所在的DP从站故障。

2.背景DB的长度访问错误,可能是背景DB没有下载或者程序访问地址超出了背景DB的范围。

提问者对于答案的评价: