问题一:成功打开服务器上的多用户项目后,在客户端激活不了,如何解决?
问题二:装载服务器项目的数据包后,组态好客户端,激活后老是提示找不到启动画面,如何解决?
问题三:其他常用WINCC网络拓扑具体部署介绍(WINCC软件环境配置和授权)?
问题四:网络拓扑为:一对冗余I/O服务器,上层接(一台OPC服务器和一台WEB服务器),实现负载分流,请问各自的服务器如何部署授权和软件环境?冗余 I/O服务器和(OPC服务器及WEB服务器)以什么方式交互数据为最佳(整体架构实现PLC最优循环读服务和快速大批量数据访问)?
如觉得繁琐两句说不清欢迎致邮件到52863955@qq.com交流讨论
小弟竭尽所能报答各位热心大侠。
最佳答案
see the link below
- Ensure you can ping the server on both IP address and computer name
- Ensure the SIMATIC Shell folder llists the server and project state correctly on the client
- Hardcode the network speed on the network cards on both client and server
- Delete server data package, check file is deleted in Windows Explorer and recreate package
- Ensure the exact same version of WinCC is on client and server
- Try creating same username / password on both client and server, add the user to the Windows SIMATIC HMI and Administrator groups and log-on using this user
(more information on this at http://support.automation.siemens.com/WW/view/en/22784251)
- Check both computers are using the same timezone and clocks are synchronised
- Check both computers have same language configured in Control Panel -> Regional Settings
参考资料:http://www.automation.siemens.com/WW/forum/guests/PostShow.aspx?language=zh&PostID=19368