请教西门子专家,840D出现报警号1016 通道1轴C/C系统错误550010,做为用户维修人员应怎样处理.
最佳答案
1016 “系统错误代码550010 ”报警原因:
Here the information out of DOCONWEB 36520 DES_VELO_LIMIT % Threshold for setpoint velocity monitoring DOUBLE NEW CONF。
Maximum permissible setpoint velocity in percent of the maximum axis/spindle velocity.
With $MA_DES_VELO_LIMIT, the position setpoint is monitored for abrupt changes. If the permissible limit value is exceeded, alarm 1016 error code550010 is output.
With axes, this machine data refers to $MA_MAX_AX_VELO.
With spindles, the MD refers to the smaller one of the set velocities $MA_GEAR_STEP_MAX_VELO_LIMIT of the current gear stage or $MA_SPIND_VELO_LIMIT.
提问者对于答案的评价:
ok