CPU报警,如何处理?

CPU报警,如何处理?
CPU报警  如下   应该是I2023有问题,可是全部程序搜索找不到2023
唯有一个BUS站的诊断地址是2023,但该站通过在线监视,工作良好。
请问高手我该如何解决?

Diagnostic buffer of module CPU 317-2 DP

Order No./ Description         Component                      Version                       
6ES7 317-2AK14-0AB0            Hardware                       1                             
- - -                          Firmware                       V 3.3.1                       
Boot Loader                    Firmware expansion             A 33.9.9                      

Rack:                          0
Slot:                          2


Serial number: S C-B7TR09822011


Event 1 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/0s
Input address:  2023
User information available 
Diagnostic interrupt from substitute
Module/submodule fault
External module error
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
05:50:23.929 PM  01/21/1994


Event 2 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/0s
Input address:  2023
User information available 
Diagnostic interrupt from substitute
Module/submodule fault
External module error
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
05:50:18.236 PM  01/21/1994


Event 3 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/0s
Input address:  2023
User information available 
Diagnostic interrupt from substitute
Module/submodule fault
External module error
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
05:50:08.044 PM  01/21/1994


Event 4 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/0s
Input address:  2023
User information available 
Diagnostic interrupt from substitute
Module/submodule fault
External module error
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
05:50:00.069 PM  01/21/1994


Event 5 of 10:  Event ID 16# 3942
Module problem or maintenance necessary
Module type: Distributed I/0s
Input address:  2023
User information available 
Diagnostic interrupt from substitute
Module/submodule fault
External module error
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Incoming event
05:49:09.828 PM  01/21/1994

最佳答案

Input address:  2023  注意这里的输入地址是指诊断地址2023(BUS站的诊断地址2023),并不是指模块输入地址
解决方法:取消2023从站模拟量模块的诊断功能或下载一个空的OB82试试。