s7-300系统PLC报警记录

请哪位高手帮我解释一下下面的报警信息!
Diagnostic buffer of module CPU 315-2 DP
Event 1 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
06:16:26.261 AM  10/28/2002
Event 2 of 10:  Event ID 16# 1382
Request for automatic warm restart 
STOP due to: Power failure
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Automatic warm restart after backed up power on
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
06:16:26.259 AM  10/28/2002
Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP 
STOP due to: Power failure
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
06:16:26.126 AM  10/28/2002
Event 4 of 10:  Event ID 16# 5371
Distributed I/Os: End of the synchronization with a DP master/IO controller   on slot    2 
Number of distributed stations:   0
Incoming event
06:16:14.793 AM  10/28/2002

问题补充:
Event 5 of 10:  Event ID 16# 4300
Power on backed up 
Previous operating mode: No voltage
Requested operating mode: STOP (own initialization)
Incoming event
06:16:09.921 AM  10/28/2002
Event 6 of 10:  Event ID 16# 494E
Power failure
Previous operating mode: RUN
Requested operating mode: No voltage
External error, Incoming event
05:56:50.333 AM  10/28/2002
Event 8 of 10:  Event ID 16# 1382
Request for automatic warm restart 
STOP due to: Power failure
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Automatic warm restart after backed up power on
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
05:53:41.071 AM  10/28/2002

最佳答案

1、关键信息:
STOP due to: Power failure。
Previous operating mode: No voltage
Requested operating mode: STOP (own initialization)
Event 6 of 10:  Event ID 16# 494E
Power failure
电源故障引起的停机。
2、检测或更换电源。
3、检查所有接线。

提问者对于答案的评价:
谢谢

专家置评

已阅,最佳答案正确。