今天修改343-1模块的IP参数后,由192.168.0.2改成192.168.0.14,编译生成下载硬件,下载过程中,315cpu自动停止,后出现此种标题情况,将MM取下插到同样配置的另一台机器上(2号机),能够运行正常,将2号机的MM卡取下插到故障机(1号机)上,同样是STOP亮黄灯,SF红灯,两台机硬件配置一样,343模块的DC5V绿灯,run灯闪烁,stop黄灯。在线查看硬件配置出现图1所示。查看CPU315的诊断信息如下
STOP caused by parameter assignment error or unpermissible difference between preset and actual configuration: startup disabled
No relevance for user (SDB no.): 5
No relevance for user (Z2): 80a0 (Z3): 0605
Previous operating mode: STARTUP (warm restart)
Requested operating mode: STOP (internal)
External error, Incoming event
07:49:04.503 AM 01/01/1994
Event 2 of 100: Event ID 16# 4301
Mode transition from STOP to STARTUP
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic startup not permitted, corrections in parameter assignment, submodule, etc. necessary
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
07:49:03.927 AM 01/01/1994
07:48:39.707 AM 01/01/1994
Event 5 of 100: Event ID 16# F260:B119
Station reconnected, DP(Drive) node: 3
Outgoing event
07:45:52.678 AM 01/01/1994
Event 6 of 100: Event ID 16# 49A0
STOP caused by parameter assignment error or unpermissible difference between preset and actual configuration: startup disabled
No relevance for user (SDB no.): 5
No relevance for user (Z2): 80a0 (Z3): 0605
Previous operating mode: STARTUP (warm restart)
Requested operating mode: STOP (internal)
External error, Incoming event
查看TECHNOLOGY诊断信息如下
Dianostic buffer of module Technol
Slot: 3
Event 1 of 200: Event ID 16# F360:B281
Operating mode STOP reached
Incoming event
07:49:04.517 AM 01/01/1994
Event 2 of 200: Event ID 16# F360:B28D
Operating mode transition from STOP_U to STOP: Start
Incoming event
07:49:04.508 AM 01/01/1994
Event 3 of 200: Event ID 16# F360:B282
Operating mode STOP_U reached
Incoming event
07:49:03.941 AM 01/01/1994
Event 4 of 200: Event ID 16# F360:B28C
Operating mode transition from STOP to STOP_U: Start
Incoming event
07:49:03.928 AM 01/01/1994
Event 5 of 200: Event ID 16# F360:B281
Operating mode STOP reached
Incoming event
07:48:40.294 AM 01/01/1994
请工程师帮我看下这个该怎么解决。
问题补充:
整套CPU还处于调试阶段,我能够正常下载和上载程序,CPU损坏还能继续下载上载程序吗?修改IP的343-1模块,RUN灯闪烁,STOP灯常亮,343没有插网线连接其他外部设备。
图片说明:
最佳答案
多半是CPU坏了。 应该是硬件故障 BF是BUS FAULT,SF是SYSTEM FAULT,BF灯亮看看硬件组态有没有问题和现场模块有没有接触良好,SF灯亮在线查PLC。
报警翻译:
停止所造成的预设和实际的配置参数分配错误或不允许的区别:启动禁用
没有相关的用户(SDB没有。):5
无相关的用户(Z2):80A0(Z3):0605
以前的操作模式:启动(暖启动)
请求的操作模式:STOP(内部)
外部错误,进入的事件
07:49:04.503 AM 01/01/1994
100事件2:事件ID 16#4301
从STOP模式转换到启动
启动信息:
- 时间在上次备份电源上的时间戳
- 单处理器操作
当前/上次启动类型:
- 开关设置触发暖重启,最后接通电源备份
允许一定的启动类型:
- 允许手动暖重启
- 自动启动,不允许在参数赋值,更正,子模块等必要的
在上电时自动启动类型的上次有效操作或设置:
- 开关设置触发暖重启,最后接通电源备份
以前的操作模式:STOP(内部)
请求的操作模式:启动(暖启动)
进入事件
07:49:03.927 AM 01/01/1994
07:48:39.707 AM 01/01/1994
100事件5:事件ID 16#F260:B119
站重新连接,DP(驱动器)节点:3
离开的事件
07:45:52.678 AM 01/01/1994
100事件6:事件ID 16#49A0
停止所造成的预设和实际的配置参数分配错误或不允许的区别:启动禁用
没有相关的用户(SDB没有。):5
无相关的用户(Z2):80A0(Z3):0605
以前的操作模式:启动(暖启动)
请求的操作模式:STOP(内部)
外部错误,进入的事件
查看技术诊断信息如下
Dianostic缓冲模块的技
槽:3
提问者对于答案的评价:
谢谢,,问题已经解决,不过感谢你给我提供这么多的知识
专家置评
已阅,最佳答案正确。
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc244705.html