A M 0.0
JNB b0
OPN DB 1
L L#0
T LD 200
L 50
M001: T LB 100
L L#0
T DBD [LD 200]
L LD 200
+ 32
T LD 200
L LB 100
LOOP M001
b0: NOP 0
A M 0.1
JNB b1
OPN DB 2
L L#0
T MD 204
L 50
M002: T LB 110
L L#0
T DBD [LD 204]
L LD 204
+ 32
T MD 204
L MB 110
LOOP M002
b1: NOP 0
我现在要清除DB1和DB2的数据,DB1和DB2里面的数据设定都是一样,我先接通M0.0进行清除,程序可以运行。之后断开MO.O,接通M0.1时,运行3秒左右故障灯亮,出现问题,这是怎么回事。
图片说明:
最佳答案
语法有错误,改成这样好了
A M 0.0
JNB b0
OPN DB 1
L L#0
T LD 200
L 50
M001: T LB 100
L L#0
T DBD [LD 200]
L LD 200
+ 32
T LD 200
L LB 100
LOOP M001
b0: NOP 0
A M 0.1
JNB b1
OPN DB 2
L L#0
T LD 204
L 50
M002: T LB 110
L L#0
T DBD [LD 204]
L LD 204
+ 32
T LD 204
L LB 110
LOOP M002
b1: NOP 0
提问者对于答案的评价:
谢谢
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc244053.html