我司一台设备使用S7-300 314-6CG03-0AA0的cpu,cpu报SF报警,但是设备可以正常运行.查看诊断列表:如下:
Event 2 of 10: Event ID 16# 1381
Request for manual warm restart
STOP due to: Power failure
Startup information:
- Startup with modified system configuration
- Difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
06:45:25:986 am 12/19/99
Event 5 of 10: Event ID 16# 4300
Power on backed up
Previous operating mode: No voltage
Requested operating mode: STOP (own initialization)
Incoming event
06:44:58:935 am 12/19/99
Event 9 of 10: Event ID 16# 4301
Mode transition from STOP to STARTUP
STOP due to: Power failure
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
06:36:36:710 am 12/19/99
问题补充:
测量了电源模块AC230V输入正常,DC24V输出正常啊。
有哪位大侠帮忙翻译一下诊断。谢谢
最佳答案
第一:电源有故障;
第二: Difference between setpoint and actual configuration,组态中的配置和实际的配置不一样,有差异。
要好好检查一下。
提问者对于答案的评价:
ok