CPU 315 2DP/PN 组建PROFIBUS主从站通讯问题

CPU 315 2DP/PN 地址为2   2047  
带了1个ET200M从站地址3   2042
       1个EM227  从站地址4   
       1个ET200M从站地址5   2040

CPU 老是自动停机,加入OB86和OB122后不停机但是CPU  SF灯仍然亮
是否可以判断时候我的主从站的  PROFIBUS  DP通讯问题呢?下面是CPU诊断信息,请高手帮忙分析是什么问题!


Diagnostic buffer of module CPU 315-2 PN/DP

Order No./ Description         Component                      Version                       
6ES7 315-2EH14-0AB0            Hardware                       4                             
- - -                          Firmware                       V 3.2.7                       
Boot Loader                    Firmware expansion             A 32.9.9                      

Rack:                          0
Slot:                          2


Serial number: S C-C7UF67812012


Event 1 of 112:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  2043
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
09:38:04.087 AM  11/26/2012
(Coding: 16# 38C4  FE56  C054  07FF  07FB  0103)


Event 2 of 112:  Event ID 16# 456F
STOP caused by rack failure (OB not loaded or not possible, or no FRB) 
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
09:38:03.169 AM  11/26/2012
(Coding: 16# 456F  FF84  0000  0101  0000  0000)


Event 3 of 112:  Event ID 16# 39C4
Distributed I/Os: station Failure
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  2043
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
Priority class: 26
External error, Incoming event
09:38:03.166 AM  11/26/2012
(Coding: 16# 39C4  1A56  C054  07FF  07FB  0103)

最佳答案

Event 3 of 112:  Event ID 16# 39C4
Distributed I/Os: station Failure
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  2043
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
从上述信息可以看出是3#站的机架故障。一般原因:
、模板前连接器与模板,模板与U型总线连接器,U型总线连接器与导轨,这些之间的安装不紧固。
、接口模块有硬件故障。
、整个站的供电电源不正常。

提问者对于答案的评价:
首先谢谢这位老师,但是还有点问题,我加入了OB86和OB122块但是还是出现停机现象。3号站的数字量模块有输出,模块之间的U型连接总线都紧固过了。DP线也没问题,要不ET200M会报警。现在问题是从站的ET200M不报警,模拟量模块BF灯也正常。还会有什么原因呢?