紧急求救,请教师兄指导

CPU315 2DP/PN  上电半个小时自动停机。
现象为  LED SF亮,同时CPU 处于STOP状态,其它从站,2个ET200M和EM227模块指示灯都正常。上电后再次重复。首先我把OB1里程序清空,还是会停机,说明我的程序没问题。停机时候模块指示灯都正常,所以请教高手指点,谢谢

诊断如下请大家帮忙分析
Diagnostic buffer of module CPU 315-2 PN/DP

Order No./ Description         Component                      Version                       
6ES7 315-2EH14-0AB0            Hardware                       4                             
- - -                          Firmware                       V 3.2.7                       
Boot Loader                    Firmware expansion             A 32.9.9                      

Rack:                          0
Slot:                          2


Serial number: S C-C7UF67812012


Event 1 of 112:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  2043
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
09:38:04.087 AM  11/26/2012
(Coding: 16# 38C4  FE56  C054  07FF  07FB  0103)


Event 2 of 112:  Event ID 16# 456F
STOP caused by rack failure (OB not loaded or not possible, or no FRB) 
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
09:38:03.169 AM  11/26/2012
(Coding: 16# 456F  FF84  0000  0101  0000  0000)


Event 3 of 112:  Event ID 16# 39C4
Distributed I/Os: station Failure
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  2043
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
Priority class: 26
External error, Incoming event
09:38:03.166 AM  11/26/2012
(Coding: 16# 39C4  1A56  C054  07FF  07FB  0103)


Event 4 of 112:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:19:06.488 AM  11/26/2012
(Coding: 16# 4302  FF68  C700  0000  0810  7710)

问题补充:
首先谢谢 半瓶醋 。
我加进去了OB86和OB122,出现的现象是不停机了,但是SF灯还是亮
  3号从站配置如下
  PS307 5A
   ET200M  153-1AA03-OXBO             指示灯正常
   DO          16*24   322-1BH01-0AA0   有输出
   AI  8*13BIT   331 1KF02-OABO
   AI   8*12bit  331-7kf02-oabo   2块,BF灯正常
  AO  8*12BIT  332-5KF00 _OABO  2块  BF灯正常

检查了DP接线正确,但是屏蔽线割掉了,没有压到贴片上。


设备正在调试,只进行了数字量调试,还没有进行模拟量调试,我该怎么去检查,怎么处理?

最佳答案

Requested OB: Rack failure OB (OB86)
STOP caused by rack failure (OB not loaded or not possible, or no FRB) 
Distributed I/Os: station Failure
从上述信息看,是机架故障:
、检查模板的安装,例如模板与机架之间的U型总线连接器、模板与前连接器的安装是否紧固。
、检查从站的通讯模块或接口模块的地址设定与组态的设定是否一致。

提问者对于答案的评价:
DP头从新做,接地也弄个专线。可能是干扰吧