Diagnostic buffer of module CPU 315-2 DP
Order No./ Description Component Version
6ES7 315-2AH14-0AB0 Hardware 4
- - - Firmware V 3.3.7
Boot Loader Firmware expansion A 32.9.9
Rack: 0
Slot: 2
Serial number: S C-C8UJ13682012
Event 1 of 110: Event ID 16# 5371
Distributed I/Os: End of the synchronization with a DP master/IO controller on slot 2
Number of distributed stations: 0
Incoming event
02:19:26.825 PM 01/03/2013
Event 2 of 110: Event ID 16# 494D
STOP due to IO error
No relevance for user (Z2): 5752 (Z3): 2101
Previous operating mode: RUN
Requested operating mode: STOP (internal)
External error, Incoming event
02:19:26.111 PM 01/03/2013
Event 3 of 110: Event ID 16# 494D
STOP due to IO error
No relevance for user (Z2): 5752 (Z3): 2101
Previous operating mode: RUN
Requested operating mode: STOP (internal)
External error, Incoming event
02:19:26.108 PM 01/03/2013
问题补充:
我的系统主站用360,从站用的是361,当现场有电机启动时候,361的SF灯闪亮一下,然后CPU的SF灯常亮,CPU从运行状态切换到停止状态。后来做了一些实验,把DI所有外部信号切断,把CPU到电脑的DP插头拔下来,基本上是切除外部所有的通信,当现场有电机启动或停止时候,361的SF灯闪亮一下,然后CPU的SF灯常亮,CPU从运行状态切换到停止状态。查看了给361供电的电源模块,接线没有问题。注明:CPU供电电源,361模块供电电源都是独立的。DI/DO卡件供电电源也是独立的,希望大家能帮我分析下,到底是什么原因,启动电机或停止电机,会导致CPU停运。现场没有接地系统
最佳答案
现场经验,最有可能是24V短路引起,注意检查一下DI、DO模块的接线。
提问者对于答案的评价:
今天把PLC柜内的进线电源,从原来MCC柜分离出来,重新找了另外一个电源点,通讯正常了。开来问题是出现在,MCC柜供电一是供现场电机设备,一是供我的PLC柜,这样,当电机启动或停止时候,可能对供电电压有影响,同时影响到了我通讯模块。把结论分享给大家,希望能帮组以后碰到类似的问题。
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc242556.html