317T-2DP CPU 经常在自动运行时stop
硬件诊断信息为
Diagnostic buffer of module CPU 317T-2 DP
Order No./ Description Component Version
6ES7 317-6TK13-0AB0 Hardware 1
- - - Firmware V 2.7.0
Boot Loader Firmware expansion A 10.13.9
Technology (478257) Firmware expansion V 4.1.5
Rack: 0
Slot: 2
Serial number: S C-B4WB22792011
Event 1 of 100: Event ID 16# 497C
STOP triggered by integrated technology
Previous operating mode: RUN
Requested operating mode: STOP (internal)
External error, Incoming event
03:23:00.535 PM 02/05/2013
(Coding: 16# 497C FF84 0000 0000 0000 0000)
Event 2 of 100: Event ID 16# F360:B11B
Integrated technology: STOP by execution system, cause: Timeout (user must parameterize cycle clocks differently)
Incoming event
03:23:00.484 PM 02/05/2013
(Coding: 16# F360 B11B C450 0064 0000 0000)
Event 3 of 100: Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
03:27:54.910 PM 02/04/2013
(Coding: 16# 4302 FF68 C700 0000 0810 7710)
Event 4 of 100: Event ID 16# 1382
Request for automatic warm restart
STOP due to: Power failure
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Automatic warm restart after backed up power on
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
03:27:54.906 PM 02/04/2013
(Coding: 16# 1382 1B64 C772 494E 0810 7710)
那位大侠给分析下,是什么原因呀,怎么处理.
最佳答案
从诊断信息来看
STOP by execution system, cause: Timeout (user must parameterize cycle clocks differently)
应该是循环扫描时间超时了,在CPU属性里修改循环扫描时间应该就可以了
具体见附图
图片说明:
提问者对于答案的评价:
谢谢
最近有调整technology组态的伺服电机速度,PLC stop 次数明显减少
不知道则么样才能确诊是否是扫描周期的问题
最佳答案作者回复:
扫描周期是没法监测出来的,你把扫描周期稍稍该大点,看看还有没有停机的情况