PLC CPU频繁进入stop模式

317T-2DP  CPU 经常在自动运行时stop 
硬件诊断信息为
Diagnostic buffer of module CPU 317T-2 DP

Order No./ Description         Component                      Version                       
6ES7 317-6TK13-0AB0            Hardware                       1                             
- - -                          Firmware                       V 2.7.0                       
Boot Loader                    Firmware expansion             A 10.13.9                     
Technology (478257)            Firmware expansion             V 4.1.5                       

Rack:                          0
Slot:                          2


Serial number: S C-B4WB22792011


Event 1 of 100:  Event ID 16# 497C
STOP triggered by integrated technology
Previous operating mode: RUN
Requested operating mode: STOP (internal)
External error, Incoming event
03:23:00.535 PM  02/05/2013
(Coding: 16# 497C  FF84  0000  0000  0000  0000)


Event 2 of 100:  Event ID 16# F360:B11B
Integrated technology: STOP by execution system, cause: Timeout (user must parameterize cycle clocks differently)
Incoming event
03:23:00.484 PM  02/05/2013
(Coding: 16# F360  B11B  C450  0064  0000  0000)


Event 3 of 100:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
03:27:54.910 PM  02/04/2013
(Coding: 16# 4302  FF68  C700  0000  0810  7710)


Event 4 of 100:  Event ID 16# 1382
Request for automatic warm restart 
STOP due to: Power failure
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Automatic warm restart after backed up power on
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
03:27:54.906 PM  02/04/2013
(Coding: 16# 1382  1B64  C772  494E  0810  7710)


那位大侠给分析下,是什么原因呀,怎么处理.

最佳答案

从诊断信息来看
STOP by execution system, cause: Timeout (user must parameterize cycle clocks differently)
应该是循环扫描时间超时了,在CPU属性里修改循环扫描时间应该就可以了
具体见附图

图片说明:

PLC  CPU频繁进入stop模式  

提问者对于答案的评价:
谢谢
最近有调整technology组态的伺服电机速度,PLC stop 次数明显减少
不知道则么样才能确诊是否是扫描周期的问题

最佳答案作者回复:
扫描周期是没法监测出来的,你把扫描周期稍稍该大点,看看还有没有停机的情况

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc241806.html