上午在保存的时候,有些心急。然后就出问题了,一直提示这个问题the triggered action cannot be executed at this time check all other STEP7 applications and exit them where necessary. 打开其他没问题的程序,也没法更改,随便加一些东西保存的时候就弹出来了。望指教,是不是软件崩溃了?
最佳答案
The triggered action cannot be executed at this time. Check all other STEP 7 applications and exit them where necessary?:
1、产生的原因:
The communications module is probably already being operated with other settings (e.g. with a different transmission rate).
2、解决方法:
Please check the baud rate on the PG/PC via "Set PG/PC interface" and the baud rate of the CPU configured.。
3、详见:
STEP 7 Error Codes:
http://cache.automation.siemens.com/dnl/DQ/DQ1Njg1MwAA_770453_FAQ/STEP7_ErrorCode_engl.pdf