求助!接模拟量输入时不慎将地线接入220V高压,报错信息如下,求各位大神给出解决办法!

我在接SM335模拟量输入接线时,不慎将地线插入插排220V口中,配电箱跳闸。当时PLC不通电。SM335放在4号位的,后面还有两个FM350模块。
后来再运行时出现如下报错信息:
Event 1 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    7
DP master system ID:      1
Log. base address of the DP slave: Input address:  2046
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
Priority class: 26
External error, Outgoing event

Event 2 of 10:  Event ID 16# 3842
Module OK
Module type: Distributed I/0s
Input address:  2046
User information available 
Diagnostic interrupt from substitute
Requested OB: Diagnostic interrupt OB (OB82)
Priority class: 26
External error, Outgoing event

Event 3 of 10:  Event ID 16# 39C4
Distributed I/Os: station Failure
Address of the affected DP slave: station number:    7
DP master system ID:      1
Log. base address of the DP slave: Input address:  2046
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
Priority class: 26
External error, Incoming event

Event 4 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event

RUN之后电机短暂运行,后报错停止,SF灯亮,之后SF灯灭,无报错,单电机还是不运行。
求大神指导啊!

问题补充:
补充诊断信息:
Event 5 of 10:  Event ID 16# 1381
Request for manual warm restart 
STOP due to: STOP caused by stop switch being activated
Startup information:
...
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event

Event 6 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP 
STOP due to: STOP caused by stop switch being activated
Startup information: 
...
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
我一直用的是OB100暖启动,不知道为什么这个也报错...

最佳答案

External error, Outgoing event
Event 3 of 10:  Event ID 16# 39C4
Distributed I/Os: station Failure
Address of the affected DP slave: station number:    7
解读上述诊断信息,分布 I/O站故障,需要检查7号从站相关的硬件。

提问者对于答案的评价:
感谢阿鸣大神提供的建议,我将PLC模块分开测试的,数字量、模拟量、计数模块单独测试都是好的,最后在检查DP从站时发现PROFIBUS屏蔽线的屏蔽层部分地方烧焦了,造成接触不良,重新剥线,换了一个接口后,问题解决!

专家置评

已阅,最佳答案正确。

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc239635.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2018年12月1日
下一篇 2018年12月1日

相关推荐