S7-400冗余故障 附上诊断记录 大家帮忙分析!谢谢

附上诊断记录 大家帮忙分析!谢谢,最近几天出现了2次,重启从机架CPU就又好了。

Diagnostic buffer of module CPU 414-4 H
Order No./ Description         Component                      Version                       
6ES7 414-4HJ00-0AB0            Hardware                       1                             
– – –                          Firmware                       V 3.1.3                       
Rack:                          1
Slot:                          3


Event 8 of 120:  Event ID 16# 7855
SYNC submodule error eliminated
occurred in: Master CPU in rack 0, no relevance for user:bb
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 00
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Outgoing event
01:53:39.285 PM  02/12/2014


Event 9 of 120:  Event ID 16# 7955
SYNC submodule error 
occurred in: Master CPU in rack 0, no relevance for user:bb
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 00
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Incoming event
01:53:38.763 PM  02/12/2014


Event 10 of 120:  Event ID 16# 7955
SYNC submodule error 
occurred in: Master CPU in rack 0, no relevance for user:01
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 00
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Incoming event
01:53:38.759 PM  02/12/2014


Event 11 of 120:  Event ID 16# 7855
SYNC submodule error eliminated
occurred in: Master CPU in rack 0, no relevance for user:bb
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 00
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Outgoing event
01:43:42.486 PM  02/12/2014


Event 12 of 120:  Event ID 16# 43E3
Master CPU: Change from redundant mode to solo mode 
Previous operating mode: RUN (redundant mode)
Requested operating mode: RUN
Event occurred in the master CPU in rack 0
Incoming event
01:43:41.823 PM  02/12/2014


Event 13 of 120:  Event ID 16# 7955
SYNC submodule error 
occurred in: Master CPU in rack 0, no relevance for user:bb
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 00
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Incoming event
01:43:41.823 PM  02/12/2014


Event 14 of 120:  Event ID 16# 7955
SYNC submodule error 
occurred in: Master CPU in rack 0, no relevance for user:01
Submodule affected: Upper SYNC submodule (IFM1F)
No text available for Z3, byte 0: 0E
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
External error, Incoming event
01:43:41.816 PM  02/12/2014

问题补充:
请帮忙看是不是同步模块故障?还是同步光纤故障?是否可以定位到4哪个同步子模块。谢谢

最佳答案

参见:H-CPU的发光二极管出错显示
http://support.automation.siemens.com/CN/llisapi.dll?func=cslib.csinfo&lang=zh&objid=11312956&caller=view
在你的程序中添加OB72,可以在此块中查看信息。
组织块使用说明
http://wenku.baidu.com/link?url=BY4k-WjSF6yNaSCQDjczdOhGywg7dtwX0RCRqB6aL15_9L26cceJTIt0o_nG2jcUI-bE9J9oVKDBgG0xTCkvDt8-g3yvzzQxw2YEqAyZXhO

提问者对于答案的评价:
不错,谢谢!如果再详细点就好了,呵呵

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc235093.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2018年12月1日
下一篇 2018年12月1日

相关推荐