Event 1 of 80: Event ID 16# 530D
New startup information in STOP mode
Startup prevented by:
- STOP request exists
- Cold restart or warm restart necessary
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Operating mode: STOP (internal)
Incoming event
10:33:54.778 AM 03/13/2014
(Coding: 16# 530D FF04 C777 0041 0810 7710)
Event 2 of 80: Event ID 16# 4568
STOP caused by time error (OB not loaded, or not possible, or no FRB)
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
10:33:54.778 AM 03/13/2014
(Coding: 16# 4568 FF84 0000 0000 0000 0000)
Event 3 of 80: Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB 37)
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.775 AM 03/13/2014
(Coding: 16# 3502 FE50 C358 0000 1138 0E25)
Event 4 of 80: Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB 37)
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.771 AM 03/13/2014
(Coding: 16# 3502 FE50 C358 0000 1138 0E25)
Event 5 of 80: Event ID 16# 3502
OB request error
No relevance for user (Z1): 0000
Cause: Cyclic interrupt clock pulse generator 8
Causing OB: Cyclic interrupt OB (OB 37)
Causing priority class: 14
Requested OB: Timing error OB (OB80)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
10:33:54.735 AM 03/13/2014
(Coding: 16# 3502 FE50 C358 0000 1138 0E25)
Event 6 of 80: Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Automatic warm restart after backed up power on
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Automatic warm restart after backed up power on
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:01:51.614 AM 03/13/2014
(Coding: 16# 4302 FF68 C700 0000 0810 7710)
最佳答案
Causing OB: Cyclic interrupt OB (OB 37)
循环中断错误
Requested OB: Timing error OB (OB80)
需要下载OB80块
原因:估计是你在OB37中的程序太多,运算时间超出了OB37的中断时间。
解决办法:
1、精简OB37中的程序
2、将OB37中的程序放到OB35中
3、下载OB80块,CPU会报错,但不会停机
提问者对于答案的评价:
问题应该解决了,我将OB37的时间改长,添加OB80后就没有出现了,感谢帮助