求指导~~~该如何解决啊?
求方案
图片说明:
最佳答案
1、如何解决:由I/O引起的STOP模式?
这个问题要认真检查与I/O相关的所有之处,例如模板的安装、电源、接线及现场干扰等。如果故障原因不排斥,只通过添加OB121和OB122使之不停机,这种带故障运行方法是不安全的。必须要仔细进行论证、评估带这种故障继续运行会有什么后果。如确认是安全的才能添加OB121和OB122使之不停机。
2、Stop caused by i/o error:
上述诊断信息表明为I/O错误 user (z1): 941a
no relevance for user (z2): 000f (z3):44ab
上述诊断信息表明为I/O错误。
2、可能的原因:
转帖:
、S7-300:
A module was removed or inserted illegally.模板被拆除或安装有问题。
、 S7-400:
Failure of the module inserted/removed monitoring or error in interrupt servicing due to a defective module or due to removing or inserting a module illegally.
To correct or avoid errors:
Based on the system status lists, check the current I/O configuration detected by the CPU. Compare this with the existing configuration to see whether there are any defective modules.
· Bus error in the local or distributed I/O
To correct or avoid error:
To remove the error, you must switch the device off and then on again. If the error still occurs, check the bus connection and interface modules in the distributed I/O. Make a note of the HEX code marked as "Not user-relevant" in the detailed information for the diagnostic buffer entry and contact your manufacturer.
· This error can occur when an expansion device is switched off, for example, if an IM module is defective.
To Correct or Avoid Error:
Replace the defective module.
提问者对于答案的评价:
谢谢大家!
专家置评
已阅,最佳答案正确。
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc233737.html