这个诊断缓冲什么意思
Diagnostic buffer of module CPU 412-3 H

Order No./ Description         Component                      Version                       
6ES7 412-3HJ14-0AB0            Hardware                       1                             
- - -                          Firmware                       V 4.5.5                       
Boot Loader                    Firmware expansion             V 4.5.0                       

Rack:                          0
Slot:                          3


Serial number: SVPB7652417


Event 1 of 119:  Event ID 16# 7303
H system (1 out of 2) has gone into redundant mode
Occurred in: Master CPU in rack 0
Startup information:
- Startup without modified system configuration 
Update time in ms: 82
Requested OB: CPU redundancy error OB (OB72)
Priority class: 28
Incoming event
12:18:28.412 AM  01/01/1994
(Coding: 16# 7303  1C48  CD5B  F802  0000  0052)

问题补充:
电源型号组态错了,改了后就好了

最佳答案

问题发生在主CPU上,是没有修改系统配置的启动项。
当下列事件出现时H?CPU?的操作系统调用OB72:
??CPU?冗余丢失?
??预定的主站切换?
??同步故障?
??SYNC?模板故障?
??刷新终止?
??比较故障(例如,RAM,PIQ)?
所有处于RUN?或STARTUP?方式的CPU?随着相应的启动事件执行OB72。
在程序中增加OB72并下载到PLC中,这样在出现故障时不停机。
参见:组织块使用说明