PLC400报INTF后转为停止

有一套设备,400PLC带3路ET200M,没路都有模拟量输入\输出,数字量输入\输出,工作3--4小时,报INTF后转为停止,但PLC至于运行,设备不开,不报警。只有5分,不要嫌少呀。

问题补充:
cpu硬件诊断关键几条如下:Event 9 of 120:  Event ID 16# 39C4
Distributed I/Os: station failure
Address of the affected DP slave: station number:    4
DP master system ID:      1
Log. base address of the DP slave: Input address:  4092
Log. base address of the DP master:  16383
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Incoming event
02:25:26:820 pm  03/02/95
Event 11 of 120:  Event ID 16# 39C4
Distributed I/Os: station failure
Address of the affected DP slave: station number:    3
DP master system ID:      1
Log. base address of the DP slave: Input address:  4093
Log. base address of the DP master:  16383
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Incoming event

最佳答案

你先检查系统中是否有OB86下载到cpu,如果没有先下载一个。因为你列举的报警信息只是将CPU中没有或者破损了的OB86,这个报警信息需要一一列举出来才能分析根本问题。

提问者对于答案的评价:
wwcwwc你好,你的能否邮箱发给我,我把全部的cpu诊断信息发给你,你帮我看一下,对plc懂得不多,又找不到老师请教。

最佳答案作者回复:
嗯,可以。wwcsqwww@126.com