设备运行过程中CPU转为stop状态

设备运行过程中突然停止,联网检查发现CPU处于stop状态,SF灯常亮,查看报警信息如下,到底是什么原因引起的停机,是由于OB86引起的还是OB82,可能还有些故障信息被覆盖了,另外OB82和OB86有什么区别,我的PLC里边OB82和OB86都有,但是为什么CPU还会进入STOP状态?另外CPU能存几条故障信息?

问题补充:
Event 7 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:   32
DP master system ID:      1
Log. base address of the DP slave: Input address:  2038
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
04:14:11.331 PM  07/03/1996

Event 10 of 10:  Event ID 16# 3842
Module OK
Module type: Distributed I/0s
Input address:  2042
User information available 
Diagnostic interrupt from substitute
Requested OB: Diagnostic interrupt OB (OB82)
OB not found, or disabled, or cannot be started in the in the current operating mode
External error, Outgoing event
04:14:10.889 PM  07/03/1996

最佳答案

避免CPU进入停机,需要再PLC中下载一切组织块,OB86,,OB87,OB121OB122,不需要编程,加进去就可以了。
从文字上看,应该是32号子站出现问题了,检查32号站看看,或者下下载以上的组织块,能否让CPU不停机。

提问者对于答案的评价:
OK

专家置评

已阅,最佳答案正确。