安装gsd文件时出错

安装gsd文件时出现错误代码13:4343,这是什么原因,怎么解决啊

最佳答案

在安装GSD时,要关闭STEP7的一些窗口。
1、有关13:4343错误:
13:4343 : An update is presently not possible. In one or   more STEP 7 applications at least one GSE file or type file is being referenced.
2、原因:
In the different S7 applications there are objects (stations) open in   which DP slaves are used. Thus it is no longer possible to install   new GSD or type files, or even to update them.
3、解决办法:
Please close the station window in the hardware configuration and all   other STEP7 applications (such as NETPRO, for example) that could   access the GSD file . The Hardware Configuration application remains   open however without content. Then you can install the GSD file.

提问者对于答案的评价:
非常感谢,已经安装完成

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc213160.html