cu320报F3001

马达一按开机按钮,CU320就报F30001,过电流,我查了没有发现过载啊,是不是电机被卡住了,造成一开机就报警啊?这是F30001的信息Cause:
The power unit has detected an overcurrent condition.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- V/f operation: Up ramp set too low.
- V/f operation: Rated motor current is significantly greater than that of the Motor Module.
- infeed: High discharge and post-charging current for line supply voltage interruptions.
- infeed: High post-charging currents for overload when motoring and DC link voltage dip.
- infeed: Short-circuit currents at power-on due to the missing commutating reactor.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
Additional causes for a parallel switching device (r0108.15 = 1):
- a power unit has tripped (powered down) due to a ground fault.
- the closed-loop circulating current control is either too slow or has been set too fast.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Note:
Fault = 0 means that the phase with overcurrent is not recognized (e.g. for Blocksize device).


Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta).
- V/f operation: Increase up ramp.
- V/f operation: Check the assignment of the rated currents of the motor and Motor Module.
- infeed: Check the line supply quality.
- infeed: Reduce the load when motoring.
- infeed: Correct connection of the line commutating reactor.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
For a parallel switching device (r0108.15 = 1) the following additionally applies:
- check the ground fault monitoring thresholds (p0287).
- check the setting of the closed-loop circulating current control (p7036, p7037).

恳请大哥帮帮我,谢谢,希望详细说明一下!谢谢你们!

最佳答案

你可以尝试下述的解决方法——

1、检查电机参数是否设置正确;

2、增大变频器的斜坡上升/下降参数值;

3、检查电机的接线(星—三角)方式是否正确;

4、检查整流单元的供电电源是否正常;

5、检查整流单元进线电抗器的连接;

6、检查电机电缆接线情况;

7、检查动力电缆是否存在短路或接地故障;

8、检查动力电缆长度是否超过了限制值。

提问者对于答案的评价:
查了,这个问题偶尔犯一下!头疼啊!不过还要谢谢你

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc207394.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年11月6日 上午11:23
下一篇 2017年11月6日 上午11:23

相关推荐