如题:采用何种措施才能避免变频器的F0453故障??
最佳答案
引用:YMING
这是 MM440 01/06 英文版的对 F0453的说明,现象、对策。
F0453 Motor stalled STOP II
Quit
Refer to F0001
Cause
- up/ or down ramp too steep (excessive gradient)
- inverter connected to an already spinning motor without using the flying restart function
- motor incorrectly connected
- motor too small
- voltage boost P1611 for sensorless vector control too low
Diagnosis & Remedy
Please check the following:
- the motor connections
- increase the ramp-up time P1120 or the ramp-down time P1121
- activate the flying restart function P1200
- use a larger motor
- increase the voltage boost P1611 for sensorless closed-loop vector control
- use closed-loop vector control with encoder instead of sensorless closed-loop vector control.
- activate the V/f closed-loop control mode (P1300 less than 20) instead of closed-loop vector control
F0453 电机堵转
原因:
- 升降斜率太陡。
- 变频器启动时连接的电机仍然在旋转,变频器又没有使能捕捉再启动功能。
- 电机连接错误。
- 电机太小。
- 对于无传感器矢量控制,启动提升电压P1611设置太低。
检查和对策:
- 电机的连接。
- 提高升速的时间P1120 或 降速时间 P1121
- 使能捕捉再启动功能 P1200
- 换一个功率大点的电机。
- 对于无传感器矢量控制模式,增加启动电压 P1611。
(如果上述几项不能解决)<-我加的。
- 建议用编码器的闭环矢量控制,替代无矢量传感器闭环控制。
- 建议使用 V/f 模式的闭环控制(P1300<20),替代(P1300>=20)的闭环控制。
提问者对于答案的评价:
好
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc203663.html