S120正常运行几个月后,这几天S120中的一个伺服轴在运行过程中出现报警,代码为F07490。
S120为CU320,驱动器为6SL3120.报警有时是在停止时,有时是在轴运行中。
报警内容如下:
请高人指点一下怎么办。
F07490 EPOS: Enable signal withdrawn while traversing
Drive objects:
SERVO, VECTOR
Response:
OFF1 (OFF2, OFF3)
Acknowledgement:
IMMEDIATELY
Cause:
- for a standard assignment, another fault may have occurred as a result of withdrawing the enable signals.
- the drive is in the "switching on inhibited" state (for a standard assignment).
Remedy:
- set the enable signals or check the cause of the fault that first occurred and then result (for a standard assignment).
- check the assignment to enable the basic positioning function.
最佳答案
F07490——运行时,使能信号取消导致该故障。
检查一下,在设备运行时,是否由于某些因素导致该使能信号丢失。
提问者对于答案的评价:
hao
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc202157.html