cu320报警F07841解决方案

The signal

问题补充:
p0864里面设得是B_INF_02:r863.0,那我应该怎么查呢?报警说明里所谓的使能端子是什么啊?麻烦详解!非常感谢!

最佳答案

F07841 ——“整流单元撤消运行信号”故障。

 故障原因:

 The signal "infeed operation" was withdrawn in operation.

 - interconnection of the binector input for the signal "infeed operation" is either incorrect or missing (p0864).

 - the enable signals of the infeed were disabled.

 - due to a fault, the infeed withdraws the signal "infeed operation".

 解决办法:

 - check the interconnection of the binector input for the signal "infeed operation" (p0864).

 - check the enable signals of the infeed and if required, enable.

 - remove and acknowledge an infeed fault.

       建议你核查一下参数p0864的值是否设置正确。很多时候,F07841故障都是由于p0864的值漏设而引起的。

提问者对于答案的评价:
xiexie

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc198506.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年10月24日
下一篇 2017年10月24日

相关推荐