starter在线修改参数,点下载图标的问题

修改P1121后,点下载后,出现提示框,窗口下面出现提示
Information: ------------------------------------------------------------------
Information: SINAMICS_S120_CU320: B_INF_02: Consistency check successful
Information: SINAMICS_S120_CU320: CU_S_021: Consistency check successful
Information: SINAMICS_S120_CU320: TM31_03: Consistency check successful
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7042[1] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[3] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[2] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[1] has been exceeded.
Error: Inconsistent parts have been found during the consistency check
Error: Error on: Consistency check
Error: Error during consistency check. (ret = 0xbe130053)
请问这是什么意思呢?我下载完后,在左边一栏中绿色图标上出现两个叹号,表示参数不一致,但我又重新上传了一遍,发现我改的参数已经修改成功!在线修改参数下载需要注意什么问题吗?
请师傅们解释一下!

最佳答案

1、Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7042[1] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[3] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[2] has been exceeded.
Error: SINAMICS_S120_CU320: VECTOR_04: The value range of p7040[1] has been exceeded.
表示参数p7040设置参数错误,超出范围。

2、Error: Inconsistent parts have been found during the consistency check
Error: Error on: Consistency check
Error: Error during consistency check. (ret = 0xbe130053)
表示连续性检查错误,和p7040的设置错误有关
3、在左边一栏中绿色图标上出现两个叹号,表示参数不一致
 是你现在下传的参数存在了RAM中,和变频器的ROM中讯的参数不一致。如果你要是不把现在RAM中的参数考到ROM中,当下次断电再上电时将恢复到原来的参数。
你可以随时是用菜单或图标COPY RAM TO ROM,把参数保存在ROM中,断电不会丢失。

提问者对于答案的评价:
比较详细,xiexie

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc197205.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年8月26日 上午12:08
下一篇 2017年8月26日 上午12:09

相关推荐