之前在打开Var变量表监控的情况下,电脑意外断电2次,之后重启电脑,想重新监控就监控不了了。提示:Monitor(33:53346), (D062) Resource error:Job list full
怎么办?重装了Step 7软件也不行。
问题补充:
不想重装系统啊,程序貌似可以在线,就是点变量表的那个眼镜时,监控不了,说任务已经满了
最佳答案
错误代码:33:53346
报警信息:Resources error (D062), job list is too full
原因:The variable table (VAT) can no longer be opened although the table
could be opened previously without any problems using the same
program and with the same CPU. Probably the VAT concerned has not
be closed correctly in the CPU.
解决方案:Please switch off the power supply of your CPU and then on again. Delete
jobs no longer required (for example, deleting breakpoints, terminating the
function "Monitoring/Modifying Variables", terminating the function "Program
Status"). You will then be able to go online again with the VAT.
有专门的报错代码解决方案,如上所示!如果需要可以将文档发给你
提问者对于答案的评价:
我把PLC Stop并清空缓存后,就可以了,应该相当于断电效果。谢谢各位,感谢!!
专家置评
已阅,最佳答案正确。
原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc187904.html