Area length error when writing–CPU诊断信息咨询

840D系统配置装载软件是CPU停机,不知如何处理。诊断信息如下:
Area length error when writing
Global DB, double-word access, Access address: 74
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.459 PM 09/24/2014


Event 3 of 10: Event ID 16# 2523
Area length error when writing
Global DB, double-word access, Access address: 68
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.458 PM 09/24/2014


Event 4 of 10: Event ID 16# 2523
Area length error when writing
Global DB, double-word access, Access address: 64
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.458 PM 09/24/2014


Event 5 of 10: Event ID 16# 2523
Area length error when writing
Global DB, double-word access, Access address: 60
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.457 PM 09/24/2014


Event 6 of 10: Event ID 16# 2522
Area length error when reading
Global DB, double-word access, Access address: 28
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.457 PM 09/24/2014


Event 7 of 10: Event ID 16# 2522
Area length error when reading
Global DB, double-word access, Access address: 24
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.456 PM 09/24/2014


Event 8 of 10: Event ID 16# 2522
Area length error when reading
Global DB, word access, Access address: 22
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.456 PM 09/24/2014


Event 9 of 10: Event ID 16# 2522
Area length error when reading
Global DB, word access, Access address: 20
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.455 PM 09/24/2014


Event 10 of 10: Event ID 16# 2522
Area length error when reading
Global DB, double-word access, Access address: 16
Requested OB: Programming error OB (OB121)
Priority class: 1
Internal error, Incoming event
04:11:46.455 PM 09/24/2014

最佳答案

诊断缓冲区给出的10条信息,都是OB121引起的内部错误,所以你需要新建一个空的OB121,然后再下载到PLC里边,这些信息就没有了。
如有新的问题,再看诊断缓冲区,没有的话,应该就可以运行了,不是致命错误。

提问者对于答案的评价:
后来又重新下装了toolbox,断电重送后错误消失了

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc182886.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年6月27日 下午5:25
下一篇 2017年6月27日 下午5:25

相关推荐