请教:SIMATIC NET一些问题!!

我使用的编程器是西门子公司的FIELD PG,型号是SIMATIC FIELD PG P4,操作系统是WINDOWS 2000 SP4,PG上安装的WINCC版本为V5.1,STEP7为V5.3,SIMATIC NET是SIMATIC CP5611和SIMATIC SOFTBUS(在编程器的硬件管理器找到的),如今出现了以下几个问题,需要请教各位高手:
 1.编程器开机后,会弹出一个提示框,标题是“SIMATIC NET Synchronization Sservice”框内的内容是“An address error occurred: Assigned station address already inuse. For further information,refer to the SINEC2.LOG file in the system directory”,关闭后可以正常登录;
 2.登录后,打开WINCC快捷方式时,会弹出一个提示框:提示框的标题是Adaptive Server Aanywhere,里面的内容是(有些长,不好意思)
 Unable to initialize NT performance monitor data area; server startup continuing
 Sybase Adaptive Server Anywhere Database Engine Version 7.0.3.2149

 This software contains confidential and trade secret information of 
 Sybase, Inc.  Use, duplication or disclosure of the software and 
 documentation by the U.S. Government is subject to restrictions set forth 
 in a license agreement between the Government and Sybase, Inc. or other 
 written agreement specifying the Government's rights to use the software 
 and any applicable FAR provisions, for example, FAR 52.227-19.
  
 Copyright 1989-2001 Sybase, Inc.  All rights reserved.
 All unpublished rights reserved.
  
 Sybase, Inc. 6475 Christie Avenue, Emeryville, CA 94608, USA
  3184K of memory used for caching
 Minimum cache size: 3184K, maximum cache size: 262144K
 Using a maximum page size of 4096 bytes
 Starting database "CC_QingHai__04-11-11_13:12:57" (D:\work\QingHai_os\QingHai_os.db) at Fri Oct 17 2008 14:43
 Transaction log: QingHai_os.log
 Starting checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 Finished checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 Database "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) started at Fri Oct 17 2008 14:43
 Database server started at Fri Oct 17 2008 14:43
 Trying to start NamedPipes link ... 
     NamedPipes link started successfully 
 Trying to start TCPIP  link ... 
     TDS (TCPIP) link started successfully 
 Now accepting requests
 Starting checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 Finished checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 Starting checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 Finished checkpoint of "CC_QingHai__04-11-11_13:12:57" (QingHai_os.db) at Fri Oct 17 2008 14:43
 如果最小化该提示框,即在右下角系统托盘形成一个运行项,若关闭该提示框,则会弹出一个Warning警告框:"One or more connections are still open,close database server anyway?"
 然后在单击WINCC菜单中的TAG管理器时,就会弹出一个错误信息“HResult Error",内容是:“0X80004005:UNSPECIFIED ERROR",关闭这个警告框又会弹出“DATABASE ERROR"警告框,内容是“Database table could not be opend”。
 以上就是我的编程器出现的问题,在借给别人之前从来没有出现过此类问题,而且也没有Adaptive Server Aanywhere这个不知是何物的东东,还请各位高手指点一二,该如何去恢复我的宝贝PG!!!

问题补充:
T-C4,你给我的第一个网络链接打不开啊,很郁闷啊!不知道还有没更好的办法解决?以前我使用这几种版本的软件都没有发生过冲突,而且这都是西门子的工程师给选择安装的,我想不会是版本兼容的问题吧?
 呵呵,还望指教啊!!!很急的,谢谢!

最佳答案

1. 应该是之前某次使用时总线故障的信息在日志中未被确认所致。楼主可以参考以下链接清除Windows2000的系统日志即可解决:
   http://support.automation.siemens.com/CN/view/zh/18737455
   2. 应该是楼主的软件不兼容所致。WinCC V5.1的亚洲版只兼容到Step7 V5.2 SP1,并不兼容Step7 V5.3以上版本。楼主描述的系统任务栏右下角系统托盘上出现的应该是个SQL的红黄色标志,一般当Sybase SQL Anywhere出错时会出现。Sybase SQL Anywhere是WinCC V5.x的后台数据库,安装时WinCC时默认安装上的,在“控制面板”--“添加/删除程序列表”中可以看到。楼主还是换WinCC V6.x吧。
   WinCC V5.x/V6.x的兼容性列表可以参考以下链接:
   http://support.automation.siemens.com/CN/view/zh/21927667
   http://support.automation.siemens.com/CN/view/zh/21927773
  WinCC V5.1 SP1/SP2只限于欧洲版,亚洲版没有SP。

 问题补充:
 把链接的内容拷贝如下,大致的意思是打开“控制面板”--“管理工具”--“事件查看器”,右键“系统日志”,清除即可;如果需要保存,可以另存之后再清除。如果没有其它的要求,最好把应用程序和安全日志都清除掉。

 QUESTION:  
 For no apparent reason I get a message from the SIMATIC NET Synchronization Service. How can I avoid this? 

 ANSWER:  
 You get a message from the SIMATIC NET Synchronization Service that refers to the file SINEC2.LOG. The message comes from a pop-up mechanism that keeps on wanting to report an event which actually occurred in the past. Acknowledge the error message concerned as follows: 

 Open the "Event Display" via Start > Settings > Control Panel > Administration. 
 Mark "System Log" and then "Right click > Delete All Events". 
 You are prompted as to whether you want to save the "System Log". If you wish, you can save the events.
 The events can then be displayed again later via "Procedure > Open Log File".
 Note
 The following message is generated in the Sinec2.log file during computer startup: 

 The system sleep operation failed
 11/15/2004 08:25:08 Event Type: E Event ID: 002B
 In this case to acknowledge you also delete the event display as described above.

提问者对于答案的评价:
我试过了,开机后的提示已经消除了,但是“Adaptive Server Aanywhere”依然会出现,如若关闭,问题依旧,单击WINCC菜单中的TAG管理器时,依然会弹出一个错误信息“HResult Error",内容是:“0X80004005:UNSPECIFIED ERROR",关闭这个警告框又会弹出“DATABASE ERROR"警告框,内容是“Database table could not be opend”。所以我在想是不是PG上的网络驱动有问题啊??需不需要重新安装SIMATIC NET呢?

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc180822.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年6月24日
下一篇 2017年6月24日

相关推荐

  • 两台PLC和两台上位机组成的以太网通讯

    我用两台PLC,各挂有CP343-1,配两台上位机通过交换机组成的以太网通讯,两台上位机要都能访问两台PLC的数据,请问应该重要设置通讯参数,越详细越好 最佳答案 S7300与WI…

    SIMATIC Net 2017年6月10日
  • CP343-1 作为IO设备与1200通信

    本来想做300profinet通讯,将1200作为智能IO挂载上去,但是买的CP343-1版本只有V2.1太低,不能挂载1200 4.0以上版本。所以想反过来,将1200…

    SIMATIC Net 2017年6月3日
  • X204-2交换机

    环型网络中,有12个X-204-2交换机组成,网络设置为自动检测冗余管理器。1#交换机为冗余管理器,当环网中断时,为什么2#管理器的RM灯绿色闪烁?这是正常情况吗?还是说明1#交换…

    SIMATIC Net 2017年5月31日
  • VB6.0访问SIMATIC NET V8.1

    我做了一个VB6.0的程序,连接OPC、读、写,都可以,但是唯独刷新不行。运行起来就是一直提示超下限。Private MyOPCServer As O…

    2017年6月4日
  • 和dcs通讯方案及cpu选型

    我有一个项目要求DI136 DO100 AI16 A016,我选择如图片所示硬件。请问各位:1、戴尔上位机用wincc与plc怎么通讯,要加什么通讯模…

    SIMATIC Net 2017年6月8日
  • S7-400H 3台上位机 双路链接 NetPro的下载问题

    一套S7-400H(含CP443-1),3*立和S7-400H通信的上位机WinCC,每台上位机内插2块CP1613组成双路径冗余网络。在做第一台上位机时,根据冗余指南里面的说明,…

    SIMATIC Net 2017年6月9日
  • win 8 系统为什么安装不上step7

    sStep7 Professional 2010  在win8系统上安装 最佳答案 不兼容。一定要用这个系统那么就安装个虚拟机。 提问者对于…

    SIMATIC Net 2017年6月5日
  • 串行通信中的奇偶校验到底准不准?

    奇校验时,是把数据位中的1与奇校验的1加起来,判断是否是奇数,如果不是奇数,证明数据受到干扰,我想的问的是,数据受干扰难道只是一位变成1?刚好让它校验的值为偶了????干扰难道不能…

    SIMATIC Net 2017年6月9日
  • 802D的外部程序传输

    使用外部程序命令,802D在传输了一段程序后WINPIC就停止传输了,机床的铣刀依然在转,但不再进给切削,程序停止了,剩下的部分再也不传了,也未看见又提示或报警,怎能让后面的程序继…

    SIMATIC Net 2017年6月19日
  • 求!图尔克BL20系列模块手册

    第一次接触这种模块  谢谢 高手 指教 最佳答案 参考:《图尔克BL20参考手册》——>http://www.gongkong.com…

    SIMATIC Net 2017年6月11日