CPU314运行一段时间,就停止了

不用做别的,只要停止再打到run就好了,不需要处理其他,后来我把别的机器cpu拿来,装上也是出现这种情况,看了程序块OB80-87,ob100  101  102   122 都有,这次清空卡以后下装了,后代带的是IM365   5个ai8*12bit,下排是1个bl00   bh01,ai8*12bit。这次报错是
Event 1 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic startup not permitted, corrections in parameter assignment, submodule, etc. necessary
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
02:35:30.248 AM  07/11/1999


Event 2 of 10:  Event ID 16# 1381
Request for manual warm restart 
STOP due to: STOP caused by I/O management
Startup information:
- Startup without modified system configuration 
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic startup not permitted, corrections in parameter assignment, submodule, etc. necessary
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up 
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
02:35:30.248 AM  07/11/1999


Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP 
STOP due to: STOP caused by I/O management
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic startup not permitted, corrections in parameter assignment, submodule, etc. necessary
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
02:35:30.151 AM  07/11/1999

Event 8 of 10:  Event ID 16# 5961
Parameter assignment error in parameters for central S7 modules
subrack 1
Slot    6
Error type: Slot configured for CPU is not occupied or is occupied by a place holder, or a station 
has failed or the switched I/O system has lost its redundancy. 
Data record number: 255
Operating mode: STOP (internal)
External error, Incoming event
11:43:00.574 PM  07/10/1999
高手指导一下

最佳答案

、STOP due to: STOP caused by I/O management
、Error type: Slot configured for CPU is not occupied or is occupied by a place holder, or a station 
、Slot    6
、Error type: Slot configured for CPU is not occupied or is occupied by a place holder, or a station has failed or the switched I/O system has lost its redundancy.  
、Operating mode: STOP (internal)
、External error, Incoming event
从上述关键诊断信息中来看,引起停机的可能原因是I/O模块故障。
、检测槽6中I/O模块安装、供电及接线是否正常。
、模块是否设置了硬件中断诊断功能。

提问者对于答案的评价:
我换了6号模块,电源模块,看看能不能好

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc169662.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年6月11日
下一篇 2017年6月11日

相关推荐