1. Set yourPG Interface to CP5611(MPI)
 ConnectyourFieldPG to theCPU withtheMPI Cable
 2. Open theFolder"Ethernet" in theSimaticManagerChoosetheCPU, 3whichyoureplacedand clickon theDownload Button5. TheProgramwill askyouforsomeSettings. All thisshouldberight, so onlyclickon OK
 6. After thesestepsyoucanchangeyourPG Interface back to Ethernet, and thenyouhaveto
 download all Blocks
 For thisyouopentheFolder"Blocks" in theSimaticManager and markall Blocks except
 "Systemdata"
 Butbeforeyoudownload all Blocks, youhaveto stoptheCPU!!!!
 Makeright mouseclickon anyBlock and press Download7. After thisyoucanstart yourCPU again, and everythingshouldworklikebefore
 8. Butyouhaveto loadall Parameterfiles in theVisualisationSystem again
 9. Youalso haveto settheTime on theCPU. For this, opentheHardware Configurationagain,
 goonline and makeright mouseclickon CPU and press "Set Time of Day"这是更换CPU的步骤,

问题补充:
主要是步骤6和8

最佳答案

1.设置PG接口为CP5611(MPI),把PG(计算机或其他设备)用MPI电缆连接。
 2.在simatic manager中打开Ethernet"选中你要替换(参数)的CPU单击“下载”按钮。
 5.程序会要求你输入一些设置,因为默认的设置都是对的所以只要单击OK即可。
 6.上述操作完成后你可以把PG接口改为Ethernet,然后下载所有程序块。为此你需要打开simaticmanager的blocks,然后选中除systemdata之外的所有块,但是下载之前你必须把cpu置于停止状态。确认所有的块都被选中后然后下载。
 7.操作完成后你可以重启CPU,所有东西都会和从前一样。
 8.但是你必须再次把参数文件上传到组态中。
 9.另,你必须设置CPU中的时间。打开“硬件组态”,设为在线状态,右击(双击)CPU后选中“设置时间日期”。
 