Event 1 of 10: Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:11:40.089 PM 09/15/1995
(Coding: 16# 4302 FF68 C700 0000 0813 7713)
Event 2 of 10: Event ID 16# 1381
Request for manual warm restart
STOP due to: STOP caused by diagnostic interrupt (OB not loaded or not possible, or no FRB)
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
09:11:40.088 PM 09/15/1995
(Coding: 16# 1381 1B64 C772 456A 0813 7713)
Event 3 of 10: Event ID 16# 4301
Mode transition from STOP to STARTUP
STOP due to: STOP caused by diagnostic interrupt (OB not loaded or not possible, or no FRB)
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
09:11:39.989 PM 09/15/1995
(Coding: 16# 4301 FF46 C772 456A 0813 7713)
Event 4 of 10: Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number: 2
DP master system ID: 1
Log. base address of the DP slave: Input address: 2047
Log. base address of the DP master: 1023
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
09:09:15.917 PM 09/15/1995
(Coding: 16# 38C4 FE56 C054 03FF 07FF 0102)
最佳答案
最后一段看出来是因为DP地址是2的站通讯故障,而且程序里面没有OB86组织块
前面3条,是手动请求暖启动的信息
提问者对于答案的评价: