300PLC运行后自动中断

Event 1 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
09:11:40.089 PM  09/15/1995
(Coding: 16# 4302  FF68  C700  0000  0813  7713)


Event 2 of 10:  Event ID 16# 1381
Request for manual warm restart 
STOP due to: STOP caused by diagnostic interrupt (OB not loaded or not possible, or no FRB)
Startup information:
- Startup without modified system configuration 
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up 
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
09:11:40.088 PM  09/15/1995
(Coding: 16# 1381  1B64  C772  456A  0813  7713)


Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP 
STOP due to: STOP caused by diagnostic interrupt (OB not loaded or not possible, or no FRB)
Startup information: 
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types: 
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
09:11:39.989 PM  09/15/1995
(Coding: 16# 4301  FF46  C772  456A  0813  7713)


Event 4 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    2
DP master system ID:      1
Log. base address of the DP slave: Input address:  2047
Log. base address of the DP master:   1023
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
09:09:15.917 PM  09/15/1995
(Coding: 16# 38C4  FE56  C054  03FF  07FF  0102)

最佳答案

最后一段看出来是因为DP地址是2的站通讯故障,而且程序里面没有OB86组织块
前面3条,是手动请求暖启动的信息

提问者对于答案的评价:

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc126873.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2017年5月28日
下一篇 2017年5月28日

相关推荐